| Standard | IEC/EN 60898-1 | ||||
| Protection | Overcurrent and short circuit | ||||
| No. of poles | 1P,2P,3P,4P,1P+N,3P+N | ||||
| Rated voltage (Ue) | 240/415V~ | ||||
| Rated currents (In) | 63,80,100,125A |
| Rated short-circuit capacity (Icn) | 6kA |
AC miniature circuit breaker (AC MCB) is a widely used low-voltage terminal protection device, almost ubiquitous in the distribution boxes of modern buildings.
Its core functions are twofold: first, it allows for manual control of circuit on/off like a switch; second, and more critically, it provides automatic protection. When an overload or short circuit occurs in the circuit, it can quickly and automatically cut off the power supply, effectively preventing equipment damage and electrical fires.
| Standard | IEC/EN 60898-1 | ||||
| Protection | Overcurrent and short circuit | ||||
| Type of trip | Thermo-magnetic | ||||
| No. of poles | 1P,2P,3P,4P,1P+N,3P+N | ||||
| Rated voltage (Ue) | 240/415V~ | ||||
| Rated currents (In) | 63,80,100,125A | ||||
| Rated frequency | 50/60Hz | ||||
| Rated short-circuit capacity (Icn) | 6kA | ||||
| Rated impulse withstand voltage (Uimp) (1.2/50μs) | 4kV | ||||
| Dielectric test voltage | 2kV (50/60Hz, 1 min.) | ||||
| Thermal tripping characteristics | (1.13-1.45) x In | ||||
| Thermo-magnetic release characteristic | C:(5-10) x In, D:(10-20) x In | ||||
| Electrical life | 4,000 Cycles | ||||
| Mechanical life | 10,000 Cycles | ||||
| Contact position indicator | green OFF / red ON | ||||
| Protection degree | IP20 | ||||
| Ambient temperature | -5℃ to +40℃, Max.95% humidity | ||||
| Terminal connection type | Cable/Pin-type busbar | ||||
| Max. terminal size for cable | 50mm2 | ||||
| Max. tightening torque | 3.5N.m | ||||
| Installation | Mounting on 35mm DIN rail | ||||
| Incoming method | Bi-Directional |