| Model | WM8ELY-160 | WM8ELY-250 | WM8ELY-400 | WM8ELY-630 | WM8ELY-800 |
| Rated frame current Inm (A) | 160 | 250 | 400 | 630 | 800 |
| Rated operational current In (A) | 100A(40~100A) 125A(50~125A) 160A(63~160A) | 125A(50~125A) 250A(100~250A) | 400A(160~400A) | 630A(0.4~1.0In) | 630A(252~630A) 800A(320~800A) |
| Rated insulation voltage Ui (V) | 1000V | ||||
| Rated impulse withstand voltage Uimp (kV) | 8KV | ||||
| Rated operational voltage Ue (V),AC 50/60Hz | AC400V | ||||
| Breaking capacity code | H | ||||
| Number of poles | 4P | ||||
| Rated service short circuit breaking capacity Ics (kA) | 50 | 50 | 50 | 50 | 65 |
| Rated ultimate short circuit breaking ca pacity Icu (kA) | 65 | 65 | 70 | 70 | 85 |
| Rated short-time withstand current Icw (kA) | 10kA/1S | 10kA/1S | 10kA/1S | 10kA/1S | 20kA/1S |
| Rated residual making and breaking capacity l△m (kA) | 25%lcu | ||||
| Standards | IEC60947-2 | ||||
| Utilization category | B | ||||
| Isolation function | ■ | ||||
| Trip unit type | Electronic | ||||
| Residual current tripper type | Electronic | ||||
| Rated residual operating current l△n (mA) | 50,100,200,300,500,800,1000mA (AC type) | ||||
| Breaktime | 0.1~2s (Adjustable) | ||||
| Limit not drive time(s) | 0.06s,0.08s,0.1s,0.2s,0.3s,0.4s,0.5s,0.6s,0.7s,0.8s,0.9s,1.0s | ||||
| Mechanical life (times) | 7000 | 7000 | 4000 | 4000 | 2500 |
| Electrica llife (times) | 1000 | 1000 | 1000 | 1000 | 500 |
| Communications protocol | DL/T 645; Modbus-RTU(requires user customization) | ||||
| Communications rate | 600bps, 1200bps, 2400bps,4800bps, 9600bps, 19200bps | ||||
WMSELY series offers a range of earth leakage MCCBs with an electronic trip unit, featuring an LCD display that provides AC type protection against residual current These MCCBs are suitable for use with AC 5OHz, rated voltage of 6soVand below, and rated current up to 800A.
Frame size: 160A,250A,400A,630A,800A
Number of poles: 4P
Rated operational voltage Ue (V/AC): 230/400/415/690
Trip unit type: electronic type
Breaking capacitycode: H
Installation method: Fixed type; plug-in type